3: INSTALLATION AND WIRING
« FC4A MICROSMART USERS MANUAL » 3-11
Installation in Control Panel
The MicroSmart modules are designed for installation in a cabinet. Do not install the MicroSmart modules outside a cabi-
net.
The environment for using the MicroSmart is “Pollution degree 2.” Use the MicroSmart in environments of pollution
degree 2 (according to IEC 60664-1).
When installing the MicroSmart modules in a control panel, take the convenience of operation and maintenance, and resis-
tance against environments into consideration.
All-in-One Type CPU Module
Slim Type CPU Module
20 mm minimum
Front Panel
Wiring Duct
20 mm minimum
20 mm minimum
20 mm minimum
40 mm
minimum
40 mm
minimum
80 mm
minimum
Front Panel
20 mm minimum
Wiring Duct
20 mm minimum
20 mm minimum
20 mm minimum
40 mm
minimum
40 mm
minimum
80 mm
minimum